A2L · GWP 466

Refrigerant R454B

R454B combines R32 and R1234yf for new air conditioning systems, heat pumps and chillers specifically designed to use it. It offers operating properties close to R410A with a lower GWP. Supplied in a green returnable cylinder containing 10 kg.

Technical specifications

Composition R32 68,9 % / R1234yf 31,1 %
GWP 466
Safety class A2L
Package 10 kg / returnable cylinder
Boiling point -50,5 °C
Oil type POE

Key properties

  • GWP 466 (AR4) and zero ozone depletion potential (ODP)
  • Composition: 68.9% R32 and 31.1% R1234yf by mass
  • A2L safety class: lower toxicity and mild flammability
  • Compatible with POE oils subject to equipment manufacturer requirements

Applications

New residential and commercial air conditioning, split and multi-split systems, heat pumps and chillers.

Equipment suitability

Use only in equipment approved for R454B and A2L refrigerants. It is not a drop-in service replacement for R410A in existing equipment without assessment and manufacturer approval.